For in-building risers we list: Ames Fire and Waterworks Series IBR, or a Watts Series TR, or a Zurn Model WBR. Ames: https://www.watts.com/products/plumbing-flow-control-solutions/risers/ibr Watts: https://www.watts.com/products/plumbing-flow-control-solutions/risers/tr Zurn: https://www.zurn.com/products/water-safety/backflow-prevention/model-wbr

Step one. Check the gauge. The built in gauges sometimes don't tell the truth. You can get a gauge which goes onto one of the drain fittings at a big box....

The expansion tank needs to be adjusted to the cold system pressure when it is completely empty of water and isolated from the system. Only way to do it.

All A1171 ABA ADA ASCE 7 ASME A17.1 ASTM E1354 Blog Thread Daily Discussion Design-documents EN 12845 Explosion Protection Explosion-protection-prevention Fire Detection And Alarm Systems Fire Dynamics Flammable And Combustible Liquids Flammable-combustible-liquids FM Global Human-behavior IBC ICC 500 IFC IMC IPC IRC ISO Means Of Egress NBC NFPA 1 NFPA 10 NFPA 101 NFPA 11 NFPA 110 NFPA 1142 NFPA 1221 NFPA 13 NFPA 13D NFPA 13R NFPA 14 NFPA 15 NFPA 16 NFPA 17A NFPA 20 NFPA 2001 NFPA 214 NFPA 22 NFPA 220 NFPA 24 NFPA 241 NFPA 25 NFPA 291 NFPA 30 NFPA 307 NFPA 30B NFPA 33 NFPA 400 NFPA 409 NFPA 415 NFPA 495 NFPA 497 NFPA 5000 NFPA 502 NFPA 54 NFPA 55 NFPA 654 NFPA 68 NFPA 70 NFPA 701 NFPA 72 NFPA 75 NFPA 770 NFPA 82 NFPA 855 NFPA 90A NFPA 92 NFPA 96 NICET OBC OSHA Passive Building Systems PE Prep Guide PE Prep Series PE Sample Problems Poll Smoke Management Special Hazard Systems UFC 3-600-01 UFC 4-021-01 UPC Updates Water Based Fire Suppression Weekly Exams

We use Ames exclusively, unless the particular situation requires we build a stub out. I can think of only one occasion where we encountered an issue with an Ames IBR.

October 2024 September 2024 August 2024 July 2024 June 2024 May 2024 April 2024 March 2024 February 2024 January 2024 December 2023 November 2023 October 2023 September 2023 August 2023 July 2023 June 2023 May 2023 April 2023 March 2023 February 2023 January 2023 December 2022 November 2022 October 2022 September 2022 August 2022 July 2022 June 2022 May 2022 April 2022 March 2022 February 2022 January 2022 December 2021 November 2021 October 2021 September 2021 August 2021 July 2021 June 2021 May 2021 April 2021 March 2021 February 2021 January 2021 December 2020 November 2020 October 2020 September 2020 August 2020 July 2020 June 2020 May 2020 April 2020 March 2020 February 2020 January 2020 December 2019 November 2019 October 2019 September 2019 August 2019 July 2019 June 2019 May 2019 April 2019 March 2019 February 2019 January 2019 December 2018 November 2018 October 2018 September 2018 August 2018 July 2018 June 2018 May 2018 November 2017 October 2017 September 2017 August 2017 July 2017 June 2017 November 2016 October 2016 July 2016 June 2016

Thank you all for the helpful replies. It's been a hectic day. Let me answer a little and then try to take and post pics tomorrow.I bought a liquid filled gauge and attached it to the hose bib on the boiler. Surprisingly the original gauge is tracking right along with it.The expansion tank was originally 1/2 to 2/3 full of water. During my reconfiguration, I pumped it up to 20 psi. But then it only was filling the top 2 or 3 inches, so I let a little air out, bringing it down to 17 psi.When I let a little water out of the system, the pressure drops. But then it climbs right back even though I have adjusted the PRV. I need to try setting it to 12 psi tomorrow when it is at ambient.Again, thanks all, and I'll be back tomorrow.Jay

The expansion tank needs to be adjusted to the cold system pressure when it is completely empty of water and isolated from the system. Only way to do it.

There is a major misunderstanding with the expansion tank pressure. You need to start at 12 PSI air pressure in the tank and set the boiler feed cold (ambient) temperature to 12 psi. They both need to match. [huge snip]

The IBR is pretested, so normally, as long as the gasket isn't compromised when connecting the supply, you should be good to go.

Image

Image

Image

As a fitter, an IBR is much easier. A traditional stub out generally requires making up at least 1 MJ gland where as, the IBR doesnt.