RPDAs are intended for use in continuous and non- continuous pressure installations, in back-siphonage and backpressure conditions. The RPDA is intended to provide protection in low and high hazard situations.

DCDAs are for use in both continuous and non- continuous pressure applications, in back-siphonage and backpressure conditions. The DCDA is intended to provide protection in low hazard situations only.

Wall hydrantfire protection

Wall hydrantvs hose bibb

This assembly is intended for use in both continuous and non-continuous pressure applications., in both back-siphonage and backpressure conditions. A DC is intended to provide protection in low hazard situations.

PVB assemblies are intended for use in both continuous and non-continuous pressure applications, in a back-siphonage condition only. A PVB is intended to provide protection in low hazard and high hazard situations.

Wall HydrantBox

RPs are used for continuous and non-continuous pressure applications, in back-siphonage and backpressure conditions. The RP is intended to provide protection in low and high hazard situations.

Dual Checks are designed for use in low hazard applications where a fully approved, testable backflow preventer is not required. Check with the local authority having jurisdiction for acceptance.

©   2024  Josam • Michigan City, IN. • 800-365-6726     Accessibility | Privacy | Terms of Use | CCPA Request Web Form | Login

A device containing a float-check, a check seat and an air inlet port. For both low and high hazard applications, AVBs are intended for use in a non- continuous pressure application (no more than 12 hours of pressure per 24 hour period), in a back- siphonage condition only.

WoodfordWall Hydrant

Image

Typically built 35+ feet high, barometric loops protect against back-siphonage, based upon the principle that a water column, at sea level pressure, will not rise above 33.9 feet.